Measured Medium | Air or non-corrosive gases |
Measurement range | +100Pa,+1000Pa,+10000Pa |
Overload pressure | 5KPa(+100Pa); 10KPa(+1000Pa); 80KPa(+10000Pa) |
Accuracy | +1.0%FS |
Operation Temperature | -20°C~80°C |
Compensated Temperature | -10°C~60°C |
Storage Temperature | -40°C~85°C |
Response time | 0.5s (default) / 1.0s / 2s / 4s |
Protection Grade | IP65 |
Pressure Connection | Concave Interface Φ 6.5 mm |
Output Signal | 4~20mA(three wire) / 0~10V / RS485 |
Control Signal | 2*SPST, 3A-30VDC / 250VAC |
PowerSupply | 16-30VDC / 24VAC+20% |
Wiring method | Cable leads from the back |
Consumption | ≤1.5W |
Housing Material | Cast aluminum housing, PC panel |
Communication | RS-485 standard interface, Modbus RTU protocol |
Key | Three tap keys |
Display | 4 bit 0.8" nixie tube |
Weight | 390g |
Size Chart:
Product model | Cable color | Red | Black | White | Green | Brown | Yellow | Gray | Blue |
LFM73X-ANXX LFM73X-ABXX | Electrical signal | +24V | GND | Vout | Iout | ||||
LFM73X-ENXX LFM73X-EBXX | Electrical signal | +24V | GND | A+ | B- | ||||
LFM73X-NRXX LFM73X-NDXX | Electrical signal | +24V | GND | Normally open contact NO1 | Public end COM1 | Normally open contactNO2 | Public end COM2 | ||
LFM73X-ARXX LFM73X-ADXX | Electrical signal | +24V | GND | Vout | Iout | Normally open contact NO1 | Public end COM1 | Normally open contactNO2 | Public end COM2 |
LFM73X-ERXX LFM73X-EDXX | Electrical signal | +24V | GND | A+ | B- | Normally open contact NO1 | Public end COM | Normally open contactNO2 | Public end COM2 |
LFM73X-HNXX | Electrical signal | +24V | GND | A+ | B- | Iout |
REMlINDER: For other product models, please refer to the information on the surface of the product for specific wiring methods.
Installation Precautions:
Installation and wiring should be performed by qualified technicians. The power should be turned off during wiring. When the transmitter is powered by a 24VAC power supply, it is recommended to use a transformer-isolated AC power supply. When the transmitter shares a 24VAC power supply with other equipment, it is necessary to ensure a reliable connection between 24V and GND. Otherwise, there may be unpredictable situation, or even damage to the equipment.