Email Us

Specification of Multi-Function Differential Pressure Transmitter LFM73



Measured MediumAir or non-corrosive gases
Measurement range+100Pa,+1000Pa,+10000Pa
Overload pressure5KPa(+100Pa); 10KPa(+1000Pa); 80KPa(+10000Pa)
Accuracy+1.0%FS
Operation Temperature-20°C~80°C
Compensated Temperature-10°C~60°C
Storage Temperature-40°C~85°C
Response time0.5s (default) / 1.0s / 2s / 4s
Protection GradeIP65
Pressure ConnectionConcave Interface Φ 6.5 mm
Output Signal4~20mA(three wire) / 0~10V / RS485
Control Signal2*SPST, 3A-30VDC / 250VAC
PowerSupply16-30VDC / 24VAC+20%
Wiring methodCable leads from the back
Consumption≤1.5W
Housing MaterialCast aluminum housing, PC panel
CommunicationRS-485 standard interface, Modbus RTU protocol
KeyThree tap keys
Display4 bit 0.8" nixie tube
Weight

390g



      Size Chart: 

LFM73_SIZE_CHART.jpg

英文-LFM73规格书20.0_2_01(1).png

Product modelCable colorRedBlackWhiteGreenBrownYellowGrayBlue
LFM73X-ANXX

LFM73X-ABXX

Electrical signal+24VGNDVoutIout



LFM73X-ENXX

LFM73X-EBXX

Electrical signal+24VGNDA+B-



LFM73X-NRXX

LFM73X-NDXX

Electrical signal+24VGND

Normally open

contact NO1

Public end

COM1

Normally open

contactNO2

Public end

COM2

LFM73X-ARXX

LFM73X-ADXX

Electrical signal+24VGNDVoutIout

Normally open

contact NO1

Public end

COM1

Normally open

contactNO2

Public end

COM2

LFM73X-ERXX

LFM73X-EDXX

Electrical signal+24VGNDA+B-

Normally open

contact NO1

Public end

COM

Normally open

contactNO2

Public end

COM2

LFM73X-HNXXElectrical signal+24VGNDA+B-Iout


REMlINDER: For other product models, please refer to the information on the surface of the product for specific wiring methods.


Installation Precautions:

Installation and wiring should be performed by qualified technicians. The power should be turned off during wiring. When the transmitter is powered by a 24VAC power supply, it is recommended to use a transformer-isolated AC power supply. When the transmitter shares a 24VAC power supply with other equipment, it is necessary to ensure a reliable connection between 24V and GND. Otherwise, there may be unpredictable situation, or even damage to the equipment.